201 Gas Burner

Power Gas Burner 150,000-399,000 BTUH

[Photo] 201GAS burner

The 201GAS burner converts from propane to natural gas with just an orifice change. No conversion kit needed. Factory packed with combustion control and gas fuel train.
Does not require a refractory liner fires with or without a combustion chamber. Proven in extensive boiler and furnace testing, these burners will meet your needs for residential gas burning applications.

Input
150,000
to 399,000 Btuh
Fuels

Natural Gas or Propane Gas
Maximum
Supply Pressure: 14 inches w.c.
Minimum
Supply Pressure: 5.0 inches w.c.
Manifold
Pressure: 3.5 inches w.c.
Control
Carlin 60200FR Microprocessor Control
4 sec. Trial for Ignition (TFI)
1.3 Sec. FFRT
Pre-purge and post-purge
Serviceman Reset Protection
Latch-up after three consecutive lockouts
Interrupted Duty Ignition
Recyle on Flame Failure
Electrical
Power:
120 vac/60Hz/1-Phase
Current:
Approximately 2.5 or 4.4 amps
Limit
Circuit Input:
120 vac/60 Hz
Motor:
1/6 or 1/4 HP, 3450 RPM, 60 Hz
Motor
Frame:
48 Frame, “N” Flange

Fuel Valve Power:
120 vac/60 Hz
Ignition
Carlin
Model 41800 solid state electronic ignition
Ignition
Voltage: 9,000 volts
Orifice
Selection
Agencies
UL
Listed: US & Canada – US per ANSI Z21.17, Canada per
CSA 2.7