601 Gas Burner

Power Gas Burner 700,000
to 1,500,000 BTUH

The 601GAS burner converts from propane to natural gas with just an orifice change no conversion kit needed. Fires negative or positive chambers from 700,000 to 1,500,000 Btuh input. Dependable direct-spark ignition of main flame for quick clean light offs. Time-tested solid state ignition and state-of-the-art microprocessor primary control technology.

Diagnostic LED lights annunciate operating mode: Self-check, Flame-on, Recycle, Lockout and Latch-up. Factory-packaged with combustion control and gas train (assembled & shipped loose, also available as knockdown). Shipped completely pre-wired for easy installation and start-up (knockdown version also available). High-efficiency, compact flame pattern design ensures clean, quiet operation. Does not require a refractory liner fires with or without a combustion chamber. Swing-away housing design.

Input
700,000 to 1,500,000 Btuh
Fuels

Natural Gas or Propane Gas
Maximum
Supply Pressure: 14 inches w.c.
Minimum
Supply Pressure: 5.0 inches w.c.
Manifold
Pressure: 3.5 inches w.c.
Control
Carlin 60200FR Microprocessor Control
4 sec. Trial for Ignition (TFI)
1.3 Sec. FFRT
Pre-purge and post-purge
Serviceman Reset Protection
Latch-up after three consecutive lockouts

Interrupted Duty Ignition

Electrical
Power:
120 vac/60Hz/1-Phase
Current:
Approximately less than 10 amps
Limit
Circuit Input:
120 vac/60 Hz
Motor:
1/2 HP, 3450 RPM, 60 Hz, 8.4 amps

Fuel Valve Power:
120 vac/60 Hz
Ignition
Carlin
Model 41000 solid state electronic ignition
Ignition
Voltage: 14,000 volts
Orifice
Selection
Contact Carlin
Agencies
UL
Listed: US