1050FFD & 1150FFD Commercial Burners

Advanced Oil Burners
Low High Low Step Modulating – 6.0 to 13.2 GPH & 11.4 to 19.8 GPH

[Photo] 1050FFD Commercial Oil Burner
The 1050FFD and 1150FFD advanced oil burners feature Carlin’s flame-funnel combustion head design. For unmatched fuel/air mixing, smooth light-offs and quiet running. The automatically-closed air damper and low-high-low step modulation (approximately 2:1 turndown) improve efficiency by closer matching of output.

To demand and reduced stand-by losses typically savings of 15-20% in seasonal fuel usage when compared to single-stage flame retention burners. Proven for years in the field and in extensive boiler and furnace testing, these burners will meet your needs for commercial oil-burning applications.

Input
1050FFD:
High Fire:
15.0 to 25.0 GPH, Low Fire: 9.0 to
12.0 GPH
1150FFD:
High Fire:
20.0 to 35.0 GPH, Low Fire: 12.0 to
15.0 GPH
Fuels
U.S.
– No. 1 or No. 2 Fuel Oil
Canada
– No. 1 Oil or No. 2 Furnace Oil

Nozzles

(3)
45° “SS” Hago
Fuel
Unit
2-Stage,
“H” Style, 100 PSIG
Oil
Valves
(2)
Oil solenoid valves
Control
1050FFD
(To 20 GPH Only):
Carlin 60200 Primary Control
1050FFD
& 1150FFD (Over 20 GPH):
Specify Control Set
Electrical
Power:
120 vac/60Hz/1-Phase
Limit
Circuit Input (60200 Primary):
120 vac/60 Hz
Control
Circuit Load:
120 vac, 1.2 amps
Motor:

1050FFD:
1 HP, 3450 RPM, Standard 115/208-230 vac, 60 Hz, 1 Phase,
12.0/6.2 amps, Optional 208-230/460 vac, 60 Hz, 3 Phase,
3.7/1.85 amps

1150FFD: 1 1/2 HP, 3450 RPM, 60 Hz, Standard 115/208-230
vac, 60 Hz, 1 Phase, 13.4/7.4 amps, Optional 208-230/460
vac, 60 Hz, 3 Phase, 5.0/2.5 amps

Motor Frame:

1050FFD: 56C Frame
1150FFD: 56C Frame


Oil Valve Power:
120 vac/60 Hz
Damper
Motor (With End Switch):
Honeywell M436A
Ignition
Carlin
Model 41000 solid state electronic ignition
Ignition
Voltage: 14,000 volts
Agencies
UL
Listed: US & Canada

1050-1150-oil-burners1050-1150-oil-burners