702CRD Commercial Burners

Advanced Oil Burners
6.0 GPH to 13.0 GPH

[Photo] 702CRD Commerical Oil Burner

The 702CRD advanced oil burner features Carlin’s adjustable combustion head assembly for unmatched fuel/air mixing, smooth light-offs and quiet running. The automatically-closed air damper and low-high-low step modulation (approximately 1.7:1 turndown) improve efficiency by closer matching of output to demand and reduced stand-by losses.

Typically savings of 15-20% in seasonal fuel usage when compared to single-stage flame retention burners. Proven for years in the field and in extensive boiler and furnace testing, these burners will meet your needs for commercial oil-burning applications.

Input
High Fire: 6.0 to 13.2 GPH
Low Fire: 3.5 to 7.5 GPH
Fuels
U.S. – No. 1 or No. 2 Fuel Oil
Canada – No. 1 Oil or No. 2 Furnace Oil

Nozzle

(1) Required, pattern and angle vary with application
Fuel Unit
2-Stage Dual Pressure 100/300 PSIG
Oil Valves
(2) Oil solenoid valve (safety and low fire valves)
(1) Oil solenoid valve, pump mounted (high-fire valve)
Control
Carlin
60200 Primary Control
Electrical
Power: 120 vac/60Hz/1-Phase
Limit Circuit Input (60200 Primary): 120 vac/60 Hz
Control Circuit Load: 120 vac, 1.2 amps
Motor: 1/2 HP, 3450 RPM, 60 Hz, Optional 115/208-230 vac, 60 Hz, 1 phase, 8.4/3.8-4.2 amps
Motor Frame: 48-Frame, “N” Flange

Oil Valve Power:
120 vac/60 Hz
Damper Motor (With End Switch): Honeywell M436A
Ignition
Carlin Model 41000 solid state electronic ignition
Ignition Voltage: 14,000 volts
Agencies
UL Listed: US & Canada