701CRD & 801CRD Commercial Oil Burners

Advanced Oil Burners – 6.0 to 13.2 GPH & 11.4 to 19.8 GPH
High Fire Input Capacity

 

 

The 701CRD and 801CRD advanced oil burners feature Carlin’s adjustable combustion head assembly – for unmatched fuel/air mixing, smooth light-offs and quiet running.

The automatically-closed air damper and low-high-low step modulation (approximately 2:1 turndown) improve efficiency by closer matching of output to demand and reduced stand-by losses. Typically savings of 15-20% in seasonal fuel usage when compared to single-stage flame retention burners. Proven for years in the field and in extensive boiler and furnace testing, these burners will meet your needs for commercial oil-burning applications.

Input
701CRD:
High Fire:
6.0 to 13.2 GPH,
Low Fire: 3.6 to 6.6 GPH801CRD:
High Fire:
11.4 to 19.8 GPH, Low Fire: 6.6 to 8.4 GPH
Fuels U.S. – No. 1 or No. 2 Fuel Oil

Canada – No. 1 Oil or No. 2 Furnace Oil

Nozzles  Low Fire Nozzle, (1) High Fire Nozzle, pattern and angle vary with application
Fuel
Unit
2-Stage,”B” Style, 150 PSIG
Oil
Valves
(2) Oil solenoid valves
Control Carlin 60200 Primary Control
Electrical Power: 120 vac/60Hz/1-Phase

Limit Circuit Input (60200 Primary): 120 vac/60 Hz

Control Circuit Load: 120 vac, 1.2 amps

 

Motor:

701CRD: 1/2 HP, 3450 RPM, 115/208-230 vac, 60 Hz, 1 phase, 8.4/3.8-4.2 amps

801CRD: 3/4 HP, 3450 RPM, 60 Hz, 115/208-230 vac, 60 Hz, 1phase, 9.8/4.8-4.9 amps.

Optional 208-230/460 vac, 60 Hz, 3 phase, 3.0-3.2/1/6 amps

Motor Frame:

701CRD: 48-Frame, “N” Flange

801CRD: 56C-Frame

Oil Valve Power: 120 vac/60 Hz

Damper Motor (With End Switch): Honeywell M436A

Ignition Carlin Model 41000 solid state electronic ignition

Ignition Voltage: 14,000 volts

Agencies
UL
Listed: US & Canada