60200 CAD Cell

Oil Primary Control

 
[tabs_framed]
 
Features
& Benefits
  Interrupted
Duty Ignition
    Recycle
on Flame Failure
    Serviceman
Reset Protection ( Latch-up after three consecutive lockouts)
    Diagnostic
LED’s
    Valve
Delay on/motor Delay Off (Pre/Post Purge – Contact Carlin
for Available Timings)
    15
Second Trial for Ignition (TFI) Other Timings Available
    1.3
Second Flame Failure response time (FFRT)
    Alarm
Contacts
    Thermostat/aquastat
Compatible
    SMC
(Safety Monitoring Circuit) Technology
     
 
   
 
     
     
Power
Input

(Red Wire)

  12
VDC
Limit
Circuit Input

(Black Wire)

  12
VDC, 4 Milliamps
Motor
Load
  16
FLA, 80 LRA
Ignitor
Load
 
5 Amps
Valve
Load
  2
Amps
Alarm
Contacts
  24
V, AC/DC, 2 amps
Limit
Circuit Input

(Black Wire)

  12
VDC, 4 Milliamps
Operating
Temperature Limits
 

+
32°F to + 140°F

Storage
Temperature Limits
  -40°F
to +185°F
Thermostat
Anticipator Current
  0.2
amp
Cad
Cell Resistance with Flame
  R
< 1500 OHMS
Wiring
Diagram
 
Agencies
  NA
[wpfilebase tag=file id=26 /][wpfilebase tag=file id=118 /]
[/tabs_framed]