60200 CAD Cell
Oil Primary Control
[tabs_framed]
Features
& Benefits |
Interrupted Duty Ignition |
|
Recycle on Flame Failure |
||
Serviceman Reset Protection ( Latch-up after three consecutive lockouts) |
||
Diagnostic LED’s |
||
Valve Delay on/motor Delay Off (Pre/Post Purge – Contact Carlin for Available Timings) |
||
15 Second Trial for Ignition (TFI) Other Timings Available |
||
1.3 Second Flame Failure response time (FFRT) |
||
Alarm Contacts |
||
Thermostat/aquastat Compatible |
||
SMC (Safety Monitoring Circuit) Technology |
||
|
Power
Input (Red Wire) |
12 VDC |
|
Limit
Circuit Input (Black Wire) |
12 VDC, 4 Milliamps |
|
Motor
Load |
16 FLA, 80 LRA |
|
Ignitor
Load |
5 Amps |
|
Valve
Load |
2 Amps |
|
Alarm
Contacts |
24 V, AC/DC, 2 amps |
|
Limit
Circuit Input (Black Wire) |
12 VDC, 4 Milliamps |
|
Operating
Temperature Limits |
+ |
|
Storage
Temperature Limits |
-40°F to +185°F |
|
Thermostat
Anticipator Current |
0.2 amp |
|
Cad
Cell Resistance with Flame |
R < 1500 OHMS |
|
Wiring
Diagram |
||
Agencies
|
NA |