60200 Primary Control
- Interrupted Duty Ignition
- Selectable 15-Second or 30-Second TFI (1.3 Second Flame Failure Response Time – FFRT)
- Recycle on Flame Failure
- Thermostat/Aquastat Compatible
- Safety Monitoring Circuit (SMC) Technology
- Alarm Contacts
- Flame Signal Test Jack
- Valve Delay On / Motor Delay Off
- Oil Pump Bleed Assist
- Optional Early Spark Termination

Tech Specs
| Power Input (Red/White Wire) | 120 VAC, 60 Hz, 9 VA |
| Limit Circuit Input (Black Wire) | 120 VAC, 60 Hz |
| Motor Load | 10 FLA, 60 LRA |
| Ignitor Load | 120 VAC, 60 Hz, 500 VA |
| Alarm Contacts | 24 V, AC/DC, 2A |
| Nozzle Line Heater | 120 VAC, 60 Hz, 1 Amp |
| Operating Temperature Limits | 32°F to 140°F |
| Storage Temperature Limits | -40°F to 185°F |
| Thermostat Anticipator Current | 0.1 Amp, AC |
| Agencies | UL Recognized in the United States and Canada |