60200FR

The 60200FR is a programmable gas primary control. It can be easily programmed directly on the control using the 4 buttons – no extra equipment needed. The large built-in LCD screen displays the burner status and helps simplify set-up and diagnostics.

Benefits

Large LCD Screen

Built-in Alarm Contacts

Last Fault Alert

Interrupted Duty Ignition

Recessed Wiring Terminals

Diagnostic & Flame Indicator LEDs

2 Second Ignition Establishment Period

1.3 Second Flame Failure Response Time (FFRT)

SMC (Safety Monitoring Circuit) Technology

Serviceman Reset Protection:
Latch-up After Three Consecutive Lockouts

Programmable Features

Expand each section to see the specs for each feature. Those in bold are factory default settings.

Time period motor is on prior to trial for ignition. Reduces carbon formation and extends ignitor life.

Programmable settings: 0 seconds, 10 seconds, 30 seconds, 90 seconds

The flame-establishing period during ignition.

Programmable settings: 4 seconds, 6 seconds

The time period the motor is on after the call for heat is satisfied to allow for evacuation of combustion gases.

Programmable settings: 0 seconds, 10 seconds, 15 seconds, 30 seconds, 60 seconds, 2 minutes

Number of recycles allowed during a single call for heat prior to lockout

Programmable settings:None, 1, 3

Allows TT to be “jumpered” by software program.

Programmable settings:Yes, No

Allows all prior burner fault conditions stored in control to be cleared.

Programmable settings: Yes, No

Allows all factory defaults to be restored in control. It will reset and reboot the control, asking you to answer “solenoid valve” question at startup.

Programmable settings: Yes, No

Tech Specs

Power Input (Red/White Wire) 120 vac, 60 Hz, 9 VA
Limit Circuit Input (Black Wire) 120 vac, 60 Hz
Motor Load 120 vac, 60 Hz, 10 FLA / 60 LRA
Ignitor Load 120 vac, 60 Hz, 500 VA
Valve Load 120 vac, 60 Hz, 2 A
Alarm Contacts 24 V, AC/DC, 2 Amps
Operating Temperature Limits 32°F to 140°F
Storage Temperature Limits -40°F to 185°F
Thermostat Anticipator Current 0.2 A, AC
Flame Current (Minimum) 0.2 A, AC
Agencies UL Recognized in the United States and Canada