601GAS Commercial Gas Burner
Power Gas Burner 700,000 to 1,500,000 BTUH

Diagnostic LED lights annunciate operating mode: Self-check, Flame-on, Recycle, Lockout and Latch-up. Factory-packaged with combustion control and gas train (assembled & shipped loose, also available as knockdown). Shipped completely pre-wired for easy installation and start-up (knockdown version also available). High-efficiency, compact flame pattern design ensures clean, quiet operation. Does not require a refractory liner fires with or without a combustion chamber. Swing-away housing design.
|
Input
|
700,000 to 1,500,000 Btuh | |
|
Fuels
|
Natural Gas or Propane Gas
Maximum Supply Pressure: 14 inches w.c. Minimum Supply Pressure: 5.0 inches w.c. Manifold Pressure: 3.5 inches w.c. |
|
|
Control
|
Carlin 60200FR Microprocessor Control 4 sec. Trial for Ignition (TFI) 1.3 Sec. FFRT Pre-purge and post-purge Serviceman Reset Protection Latch-up after three consecutive lockoutsInterrupted Duty Ignition |
|
| Electrical | Power: 120 vac/60Hz/1-Phase
Current: Approximately less than 10 amps Limit Circuit Input: 120 vac/60 Hz Motor: 1/2 HP, 3450 RPM, 60 Hz, 8.4 amps Fuel Valve Power: 120 vac/60 Hz |
|
| Ignition | Carlin Model 41000 Solid State Electronic Ignitor
Ignition Voltage: 14,000 volts |
|
| Orifice Selection |
Contact Carlin | |
|
Agencies |
UL Listed: US |