EZ-Temp Mode: 90000A, B & C
Dual Limit Temperature Control
Operating and High Limit
Features & Benefits
- Multiple Sensor Option (1 or 2) (Using individual and/or dual sensor assemblies)
- Easy Remote Sense (Electronic sensors, wired to control)
- Smart Manual Reset (Manual reset only if operating limit doesn’t open)
- Serviceman reset protection (Latch-up after three consecutive lockouts)
- Latch-up mode shuts down the control after three consecutive lockouts and requires a special procedure to reset. This ensures the owner will call in a licensed technician to troubleshoot and correct burner problems.
- Power-independent Lockout (Power cycling won’t reset from lockout or latch-up)
- Diagnostic LED’s (Power, Call for Heat, Lockout/latch-up)
- SMC Technology (Safety Monitoring Circuit)
- Provides two limit relays. Carlin’s Safety Monitoring Circuit monitors the contacts for both relays. Lockout occures if a limit relay contact is found closed when it should be open.)
Model 90000A
|
|
|
Power Input
(Red/White Wire) |
120 vac, 11 VA | |
Contacts
|
2 Independent | |
Contact Rating
|
Full Load: 120 vac, 10 Amps Locked Rotor: 120 vac, 60 Amps |
|
Wires
|
Quantity: 6 120 vac Hot/Neutral: Red-white/white Operating Limit In/Out: Black-green/black High limit In/Out: Black-red/black-yellow Limits Out: NA |
|
Adjustable Operating Limit Range
|
Any range between 50°F to 240°F | |
Fixed High Limit Temperature
|
Any value from 160°F to 240°F | |
Fixed Differential (Subtractive)
|
Any value from 5°F to 100°F | |
Operating Temperature Limits
|
+32°F to +140°F | |
Storage Temperature Limits
|
-40°F to +185°F | |
Agencies
|
UL & ULC Listed or Recognized Component (US & Canada) | |
Model 90000B
|
|
|
Power Input
(Red/White Wire) |
120 vac, 11 VA | |
Contacts
|
2 In Series | |
Contact Rating
|
Full Load: 120 vac, 10 Amps Locked Rotor: 120 vac, 60 Amps |
|
Wires
|
Quantity: 3 120 vac Hot/Neutral: Red-white/white Operating Limit In/Out: NA High limit In/Out: NA Limits Out: Black |
|
Adjustable Operating Limit Range
|
Any range between 50°F to 240°F | |
Fixed High Limit Temperature
|
Any value from 160°F to 240°F | |
Fixed Differential (Subtractive)
|
Any value from 5°F to 100°F | |
Operating Temperature Limits
|
+32°F to +140°F | |
Storage Temperature Limits
|
-40°F to +185°F | |
Agencies
|
UL & ULC Listed or Recognized Component (US & Canada) | |
Model 90000C
|
|
|
Power Input
(Red-White Wire) |
120 vac, 11 VA | |
Contacts
|
2 In Series | |
Contact Rating
|
Full Load: 120 vac, 10 Amps Locked Rotor: 120 vac, 60 Amps |
|
Wires
|
Quantity: 3 120 vac Hot/Neutral: Red-white/white Operating Limit In/Out: NA High limit In/Out: NA Limits Out: Black |
|
Adjustable Operating Limit Range
|
Any range between 50°F to 240°F | |
Fixed High Limit Temperature
|
Any value from 160°F to 240°F | |
Fixed Differential (Subtractive)
|
Any value from 5°F to 100°F | |
Operating Temperature Limits
|
+32°F to +140°F | |
Storage Temperature Limits
|
-40°F to +185°F | |
Agencies
|
UL & ULC Listed or Recognized Component (US & Canada) |