60200 CAD Cell
Oil Primary Control
- Interrupted Duty Ignition
- Recycle on Flame Failure
- Serviceman Reset Protection ( Latch-up after three consecutive lockouts)
- Diagnostic LED’s
- Valve Delay on/motor Delay OFF (Pre/post purge – Contact Carlin for Available Timings)
- 15 Second Trial for Ignition (TFI) Other Timings Available
- 1.3 Second Flame Failure response time (FFRT)
- Alarm Contacts
- Thermostat/Aquastat Compatible
- SMC (Safety Monitoring Circuit) Technology
Power Input
(Red/White Wire) |
120 vac, 60 Hz, 9 VA | |
Limit Circuit Input
(Black Wire) |
120 vac, 60 Hz | |
Motor Load
|
10 FLA, 60 LRA | |
Ignitor Load
|
120 vac, 60 Hz, 500 VA | |
Valve Load
|
120 vac, 60 Hz, 0.3 Amps | |
Alarm Contacts
|
24 V, AC/DC, 2 Amps | |
Operating Temperature Limits
|
+ 32°F to + 140°F | |
Storage Temperature Limits
|
-40°F to +185°F | |
Thermostat Anticipator Current
|
0.1 A, AC | |
|
||
Wiring Diagram
|
||
Agencies
|
UL & ULC Recognized Component United States & Canada | |