60200 CAD Cell

Oil Primary Control

 60200 Primary Control
  • Interrupted Duty Ignition
  • Recycle on Flame Failure
  • Serviceman Reset Protection ( Latch-up after three consecutive lockouts)
  • Diagnostic LED’s
  • Valve Delay on/motor Delay OFF (Pre/post purge – Contact Carlin for Available Timings)
  • 15 Second Trial for Ignition (TFI) Other Timings Available
  • 1.3 Second Flame Failure response time (FFRT)
  • Alarm Contacts
  • Thermostat/Aquastat Compatible
  • SMC (Safety Monitoring Circuit) Technology
Power Input
(Red/White Wire)
120 vac, 60 Hz, 9 VA
Limit Circuit Input
(Black Wire)
120 vac, 60 Hz
Motor Load
10 FLA, 60 LRA
Ignitor Load
120 vac, 60 Hz, 500 VA
Valve Load
120 vac, 60 Hz, 0.3 Amps
Alarm Contacts
24 V, AC/DC, 2 Amps
Operating Temperature Limits
+ 32°F to + 140°F
Storage Temperature Limits
-40°F to +185°F
Thermostat Anticipator Current
0.1 A, AC
 
 
Wiring Diagram
Agencies
UL & ULC Recognized Component United States & Canada