015 – WIRING HONEYWELL T87 MERCURY FREE THERMOSTAT WITH CARLIN PRIMARY CONTROLS

015 – WIRING HONEYWELL T87 MERCURY FREE THERMOSTAT WITH CARLIN PRIMARY CONTROLS

It has come to our attention from technicians in the field that they have been having issues using Honeywell T87 Mercury Free thermostats with Carlin Primary controls. Through testing in our lab, we have found the Honeywell T87 Mercury Free thermostats are not backward compatible with all primary controls already existing in the field. This [...]

015 – WIRING HONEYWELL T87 MERCURY FREE THERMOSTAT WITH CARLIN PRIMARY CONTROLS2012-10-20T01:54:16-04:00

014 – IGNITOR TESTING & TROUBLESHOOTING

This test procedure consists of three tests. The first test should be the ignitor spark test. The second test is a secondary coil resistance test. The third test consists of an input current test. The following is a step by step procedure to perform these tests. It is important that all three of these tests [...]

014 – IGNITOR TESTING & TROUBLESHOOTING2012-10-20T01:54:16-04:00

013 – RESPONDING TO CONTROL LOCKOUT CALLS

  Direct Vent Issues: With the introduction of direct vent equipment, a variety of installation and service issues are being confronted. Primary among these are cross contamination and cold combustion air. On 12/26/02, we issued a Technical Service Bulletin addressing the problem of cross contamination. This is most often seen with concentric terminations (one penetration [...]

013 – RESPONDING TO CONTROL LOCKOUT CALLS2020-08-13T15:06:47-04:00

012 – DIRECT VENT APPLICATIONS AND CROSS CONTAMINATION

The increased use of direct vent appliances in the past five years has brought with it a variety of challenges/problems for the heating industry. A direct vent appliance uses neither a chimney nor a power venter. Flue gases are vented directly through the sidewall of the building using the burner to provide the necessary draft. [...]

012 – DIRECT VENT APPLICATIONS AND CROSS CONTAMINATION2020-08-13T15:06:47-04:00

011 – WARNING OF MIS-WIRING POTENTIAL WITH HONEYWELL 7184P AND 8184P VALVE DELAY ON / MOTOR DELAY OFF (PRE / POST PURGE) CONTROLS

In a technical bulletin published by another burner manufacturer an explanation of the wiring colors for pre/post purge cad cell controls was given. That bulletin stated that the limit wire on the control was "commonly red" and the L1 power was "commonly black". I feel it is IMPERATIVE that I correct that statement to avoid [...]

011 – WARNING OF MIS-WIRING POTENTIAL WITH HONEYWELL 7184P AND 8184P VALVE DELAY ON / MOTOR DELAY OFF (PRE / POST PURGE) CONTROLS2020-08-13T15:06:48-04:00