60200FR Programmable Primary Control
Features& Benefits
- Interrupted Duty Ignition
- Recycle on Flame Failure
- Serviceman Reset Protection ( Latch-up after three consecutive lockouts)
- Diagnostic & Flame Indicator LED’s
- Pre-Purge and Post-purge (contact Carlin for available timings)
- 2 Second Ignition Establishment Period
- 4 Second Trial for Ignition (TFI) Other Timings Available
- 1.3 Second Flame Failure response time (FFRT)
- Alarm Contacts
- Thermostat/aquastat Compatible
- SMC (Safety Monitoring Circuit) Technology
Power Input (Red/White Wire)
120 vac, 60 Hz, 9 VA
Limit Circuit Input (Black Wire)
120 vac, 60 Hz
Motor Load
120 vac, 60 Hz, 10 FLA, 60 LRA
Ignitor Load
120 vac, 60 Hz, 500 VA
Valve Load
120 vac, 60 Hz, 2.0 Amps
Alarm Contacts
24V, AC/DC, 2 Amps
Operating Temperature Limits
+32ºF to + 140ºF
Storage Temperature Limits
-40ºF to +185ºF
Thermostat Anticipator Current
0.2A, AC
Flame Current (Minimum)
0.8 Microamp DC
Agencies
UL Recognized (US), CUL Recognized (Canada)
60200FR Wiring to Commerical Gas Train

60200FR Wiring to EZ-Gas (120V)
60200FR Wiring to EZ-Gas (24V)
60200FR Field Wiring
-
60200FR Primary Programmable Control 60200FRNS
TFI (secs) Fixed 4Pre purge 30Post purge 30Recycles NO -
60200FR Primary Programmable Control 60200FRS
TFI (secs) ProgrammablePre purge 0, 10, 30, 90Post purge 0, 10, 15, 30, 60, 120Recycles NO