801GO Commercial Dual Fuel Burner
Specs At A Glance
Min output (BTUH) 1,400,000
Max output (BTUH) 2,499,999
Fuels Oil Gas
Control Honeywell RM7897C
Ignition 45000
Introducing the latest entry to our Dual Fuel Commercial Burner Line, the 801GO!
Features includeÉ
- Robust build designed to withstand demanding use in both Low-Fire and High-Fire
- Upgraded, state-of-the art components including our new pilot design, low profile panel with optional configurations and Siemens damper actuator
- Designed with technicians in mind for simple adjustments and servicing
- Fully assembled Gas Trains available with standard pressure, low pressure, and vent-less
- All firing rates use the same air handling parts with simple adjustments of the combustion head and air shutter
- Short lead times to get YOU the burner when YOU need it
- Use with #2 Oil & Natural Gas/ Propane
Oil Input
801 G/O [High Rate (51600B)]: High fire: 15 to 17 GPH
801 G/O [Low Rate (51600A)]: High fire: 10.4 to 15 GPH
801 G/O [Low Rate (51600A)]: High fire: 10.4 to 15 GPH
Gas Input
801 G/O [High Rate (51600B)]: High fire: 2100 to 2500 MBH
801 G/O [Low Rate (51600A)]: High fire: 1400 to 2100 MBH
801 G/O [Low Rate (51600A)]: High fire: 1400 to 2100 MBH
Fuel
No. 1 or No. 2 Fuel Oil Natrual Gas or Propane
Fuel Unit
2-Stage, 150 PSIG
Oil Valves
(2) Oil solenoid valves
Control
Honeywell RM7897C
Electrical
Power:120 vac/60Hz/1-Phase
Limit Circuit Input: 120 vac/60 Hz
Control Circuit Load: 120 vac, 1.2 amps
Oil Valve Power: 120 vac/60 Hz
Damper Motor (With End Switch): Siemens SQN71
Limit Circuit Input: 120 vac/60 Hz
Control Circuit Load: 120 vac, 1.2 amps
Oil Valve Power: 120 vac/60 Hz
Damper Motor (With End Switch): Siemens SQN71
Motor
801 G/O [High Rate (51600B)]: 1 1/2 hp, 3450 rpm, 56C-frame208-230 / 460 vac/60 hz/3-ph, 3.0-3.2 / 1.6 amps
801 G/O [Low Rate (51600A)]: 3/4 hp, 3450 rpm, 56C-frame 115 / 208-230 vac/60 hz/1-ph, 9.8 / 4.8-4.9 amps
801 G/O [Low Rate (51600A)]: 3/4 hp, 3450 rpm, 56C-frame 115 / 208-230 vac/60 hz/1-ph, 9.8 / 4.8-4.9 amps
Ignition
Gas: Carlin Model 41800 Solid State Ignitor Ignition Voltage:9000 volts
Oil: Carlin Model 45000 solid state ignitor Ignition Voltage: 14000 volts
Oil: Carlin Model 45000 solid state ignitor Ignition Voltage: 14000 volts
Agencies
UL Listed: US & Canada

-
801GO Commercial Dual Fuel Burner 51600A
Min output (BTUH) 1,400,000Max output (BTUH) 2,100,000Fuels Oil GasControl Honeywell RM7897CIgnition 45000 -
801GO Commercial Dual Fuel Burner 51600AN
Min output (BTUH) 1,400,000Max output (BTUH) 2,100,000Fuels Oil GasControl Honeywell RM7897CIgnition 45000 -
801GO Commercial Dual Fuel Burner 51600B
Min output (BTUH) 2,100,000Max output (BTUH) 2,499,999Fuels Oil GasControl Honeywell RM7897CIgnition 45000 -
801GO Commercial Dual Fuel Burner 51600BN
Min output (BTUH) 2,100,000Max output (BTUH) 2,499,999Fuels Oil GasControl Honeywell RM7897CIgnition 45000
Description